Home > Products > UPS power supply

1-3KVA Power UPS power supply

Brand: RENDA
Model: RDH1-3KVA
Updated: 2016/4/26
  • Product description
  • Scope of application
  • Product features
  • Technical parameters

RDH series special UPS (special inverter power supply) is a special power supply product designed for uninterrupted AC power supply systems such as power plants, substations, distribution stations, post and telecommunications, railways, etc., with double conversion online, zero conversion and fault bypass functions. This series of products is using advanced DSP digital control technology, high-frequency switching technology, so that the series of products better quality, better performance, easier to install and maintain.

RDH series special UPS (special inverter power supply) is a special power supply product designed for uninterrupted AC power supply systems such as power plants, substations, distribution stations, post and telecommunications, railways, etc.

◆ Fully adopt DSP digital control technology, the product is more stable and the quality is superior.

◆ DC self-start function, in DC mode, DC voltage out of range, dedicated UPS turn off the output, when it returns to normal value, dedicated UPS automatically boots.

◆ The load power factor is 0.8, which is designed according to the latest electrical equipment standards.

◆ Active input power factor correction (PFC) is as high as 0.98 or more, avoiding pollution to the power grid environment and meeting the social requirements of energy conservation and environmental protection.

◆ Wide input voltage frequency range can supply power normally even in remote areas with very harsh power environment, reducing the number of battery discharges and improving the service life of the battery.

◆ When the zero switching mains power is unstable, the conversion time of the UPS power supply mode is zero, which effectively ensures the safety and reliability of load operation.

◆ Convenient remote monitoring function, providing standard RS232 interface, optional dry contact, RS485, and network monitoring card.

Product Model 
Properties and parameters
RDH1K-48/100/220
RDH2K-48/100/220
RDH3K-48/100/220
Rated output capacity
1000VA/800W
2000VA/1600W
3000VA/2400W
Communication
Enter
Rated voltage
220Vac/230Vac/240Vac
Rated frequency
50Hz/60Hz
Input voltage range
(172~268)±7Vac
Input frequency range
(45~55)±0.5Hz
AC input harmonics
<3%.
Charge
Charging current
5-7A (charging function, optional function).
DC
Enter
DC rated voltage
48Vdc/110Vdc/220Vdc
48V
Communication systems
Rated current
19.6A
39.2A
58.8A
DC voltage range
40-58V
Enter the low voltage alarm/protection point
40/42V
Enter the high voltage alarm/protection point
58/58V
110V
Power system
Rated current
8.6
17.2
25.8
DC voltage range
90-130V
Enter the low voltage alarm/protection point
95/90V
Enter the high voltage alarm/protection point
130/130V
220V
Power system
Rated current
4.3
8.6
12.9
DC voltage range
180-260V
Enter the low voltage alarm/protection point
190/180V
Enter the high voltage alarm/protection point
260/260V
Exchange Output
Output voltage
220Vac±3% (inverter output).
Output frequency
50±5Hz (when AC input is normal), 50Hz±1% (when AC input is abnormal).
Dynamic voltage transients
<5%.
Dynamic transient recovery time
< 60ms
Waveform
Sine wave THD <3% (linear load); THD <8% (nonlinear load).
Output power factor
0.8
Overload capacity
130% for not less than 20s
Output current peak factor
3:1
DC and AC conversion time
0ms
How the panel is displayed
LCD/LED optional
Communication functions
Standard RS232+ smart slot, smart slot expandable RS485, dry node, SNMP and other monitoring functions.
Protection features
DC input overvoltage, undervoltage protection, overload protection,
overtemperature protection, short circuit protection, output overvoltage, low voltage protection
SIZE (W*H*D) MM
432*88*300
432*88*440
Weight Kg
6.5
9.5
10